Auxiliary Contact Status vs Proof-of-Flow Telemetry

#proof-of-flow-telemetry
Also called
  • Proof of Flow
  • Auxiliary Contact
  • Coupled-Physics Overlay
  • command vs feedback

Plain-English definition

The diagnostic discipline of verifying physical fluid movement through direct process measurements (differential pressure, flowmeters, motor current in amps, and temperature split) rather than trusting a starter auxiliary contact or BMS 'Run' command bit alone.

Why it matters on shift

A contactor auxiliary switch only proves an electrical relay closed: a sheared pump coupling, closed isolation valve, vapor-locked impeller, or tripped VFD output can leave zero flow behind a green 'Run' icon.

Illustrative operational example

In the illustrative NOC triage lab, overlaying pump CHW-P2B motor current (0.0 A) with header ΔP (collapsed from 24.0 to 4.2 psi) provides indisputable proof of flow loss.

Scope, code & safety boundary

During commissioning and incident response, always corroborate command state against at least two coupled physical trends (amps, ΔP, flow, and ΔT).

Related courses & interactive lab practice

IntermediateRS-202~78 min open lessons
Signal Room

Building/power monitoring & alarm triage

BeginnerRS-103~85 min open lessons
Thermal Reality

Air, chilled-water & liquid cooling

Free interactive simulator
Campus Shift · 6-Mission Browser Lab

Practice live readings and switching in "NOC Alarm Storm & 1ms SOE Triage" with no login required.

Primary standards & technical references

Practice with the equipment

Try this concept in a live scenario.

Walk through six free guided browser missions in Campus Shift, or study all nine self-paced courses from Beginner to Advanced at $399 self-paced tuition ($1,600 list, save $1,201).