Distributed-Redundant (Catcher / Reserve Bus) Topology
Plain-English definition
A capital-efficient fault-tolerant power or cooling architecture, such as four lineups serving three load blocks (4-to-make-3), where one shared reserve ('catcher') lineup automatically picks up whichever primary module faults or enters maintenance via static transfer switches.
Why it matters on shift
Once the shared catcher bus is actively carrying Load Block 1 during maintenance or a fault, Load Blocks 2 and 3 temporarily lose their redundant backup path, meaning concurrent elective maintenance on those sister blocks must be frozen.
Illustrative operational example
In an illustrative 4-to-make-3 electrical lineup rated at 1.5 MW per block, transferring Block A onto the Reserve Catcher UPS for preventive capacitor work requires holding all permits on Blocks B and C until Block A returns.
Scope, code & safety boundary
Block-redundant and catcher transfer topologies wire static switches differently across sites; always trace the stamped site one-line diagram before approving concurrent permits.