First-Out Fault Indication
Plain-English definition
The earliest latched protective relay target, local panel fault code, or millisecond-stamped alarm identifying the specific condition that initiated an equipment trip before downstream sympathy alarms cascaded across connected buses or loops.
Why it matters on shift
Pressing local 'Acknowledge/Reset' on a tripped VFD, UPS, or breaker panel before photographing and logging the display wipes out the diagnostic latch needed to separate a transient grid sag from an internal short circuit.
Illustrative operational example
In an illustrative chilled-water pump trip, recording untouched local VFD Fault Code F0001 (Overcurrent) before placing the selector in OFF tells engineers to megger motor windings rather than chasing BMS communication ghosts.
Scope, code & safety boundary
Never reset a latched electrical or rotating-machinery fault target without capturing verbatim fault codes, timestamps, and engineering clearance under site EOPs.