Sequence of Events (1 ms SOE) Log and Precision Time Sync (PTP / IRIG-B)
Plain-English definition
A chronological ledger recorded by protective relays, meters, and controllers locked to a shared precision clock, such as IEEE 1588 Precision Time Protocol (PTP) or IRIG-B, that timestamps breaker contacts, voltage sags, and trip signals to 1-millisecond resolution.
Why it matters on shift
Without synchronized millisecond clocks, clocks drifting by even two seconds across switchgear and mechanical panels scramble cause and effect, making a downstream pump trip appear earlier than the utility sag that caused it.
Illustrative operational example
In the illustrative NOC Alarm Storm lab, the 1 ms SOE log orders Feeder B sag (+0 ms), 16 CRAH VFD ride-throughs (+186 ms), and Secondary Pump CHW-P2B lockout (+636 ms), exposing the true causal chain.
Scope, code & safety boundary
Audit GPS/PTP grandmaster time-sync health routinely; an unsynchronized relay falling back to a free-running internal crystal invalidates cross-panel millisecond correlation.
Related courses & interactive lab practice
Critical power & dual-path feeds
Building/power monitoring & alarm triage
Maintenance procedures, hold gates & response
Physical & control-network (OT) security
Shift command, permits & reliability
Practice live readings and switching in "NOC Alarm Storm & 1ms SOE Triage" with no login required.
Primary standards & technical references