Infrared (IR) Thermography Burn-In Scan and Inspection Windows
Plain-English definition
Non-contact radiometric thermal imaging performed across energized switchgear, UPS terminations, PDUs, and overhead busway joints under sustained load (ideally through crystal or polymer IR inspection windows) to spot high-resistance loose lugs before insulation chars.
Why it matters on shift
An under-torqued breaker lug looks completely normal at 0 A during L2 torque checks yet glows tens of degrees hotter than adjacent phases once carrying 400 A during L5 burn-in.
Illustrative operational example
During an illustrative L5 load-bank burn-in at 85% rated current, scanning through a closed-panel IR window reveals Phase B on Tap-Off 14 running 24°C hotter than Phases A and C, catching an improperly seated stab.
Scope, code & safety boundary
Scanning through listed closed-door IR windows avoids open-panel exposure; removing bolted switchgear covers under load is energized electrical work governed strictly by NFPA 70E permits and arc-rated PPE.