Inhibited Propylene-Glycol Coolant (PG25)

#propylene-glycol-coolant
Also called
  • PG25
  • inhibited water-glycol
  • 25% propylene glycol
  • TCS coolant chemistry

Plain-English definition

A secondary liquid-cooling fluid blending roughly 25% propylene glycol by volume with 75% high-purity deionized water plus multi-metal corrosion inhibitors and biostatic buffers, used in many direct-to-chip TCS loops for shipping freeze protection and biological stability.

Why it matters on shift

Compared with pure treated water, glycol slightly lowers specific heat and raises viscosity (requiring modestly higher pump pressure for the same heat load), while helping inhibit microbial growth above ~20% concentration.

Illustrative operational example

In the illustrative Hall D scenario, Row 8 runs an explicit PG25 assumption across 25 µm strainers; if glycol concentration drifts too low from pure-water top-offs, biostatic protection degrades.

Scope, code & safety boundary

PG25 is not universal: some GPU/CPU OEMs specify inhibited treated water while others require specific OEM-qualified PG25 formulations. Never mix unapproved inhibitor brands or top off with tap water.

Explanatory diagram · CDU skid, duplex strainers & rack quick-disconnectsFacility Water System (FWS) vs Technology Cooling System (TCS)
Three-zone liquid cooling schematic showing 12.0 degrees Celsius Facility Water System plant piping on the left, a CDU stainless plate heat exchanger with 25 micron strainer and dew-point guard in the center, and a 24.0 degrees Celsius Technology Cooling System rack manifold loop on the right.

A Coolant Distribution Unit (CDU) transfers heat across a stainless plate heat exchanger while keeping building chilled water physically separate from the filtered, chemistry-controlled coolant inside server cold plates.

Read plain-text walkthrough of this diagram

Zone 1 shows the building Facility Water System supplying 12.0 degrees Celsius chilled water and returning 19.0 degrees Celsius water via a modulating two-way valve without entering white-space racks. Zone 2 shows the CDU 316L stainless brazed-plate heat exchanger, N+1 variable-speed pumps, 25 micron strainer, and dew-point guard holding supply at least 3.0 degrees Celsius above the 13.8 degrees Celsius hall dew point. Zone 3 shows the Technology Cooling System delivering 24.0 degrees Celsius clean inhibited coolant across quick-disconnect valves to GPU and CPU cold plates (78% heat) while air cooling removes the remaining 22% rack heat.

Related courses & interactive lab practice

AdvancedRS-203~85 min open lessons
AI Density Lab

High-density AI cooling & commissioning

Free interactive simulator
Campus Shift · 6-Mission Browser Lab

Practice live readings and switching in "120 kW GPU Direct-to-Chip CDU & Strainer Lab" with no login required.

Primary standards & technical references

Practice with the equipment

Try this concept in a live scenario.

Walk through six free guided browser missions in Campus Shift, or study all nine self-paced courses from Beginner to Advanced at $399 self-paced tuition ($1,600 list, save $1,201).