Rear-Door Heat Exchanger (RDHx)
Plain-English definition
A hinged liquid-cooled finned coil mounted in place of a cabinet's standard rear mesh door so hot server exhaust air passes directly through chilled-water or TCS tubes and re-enters the room at near-neutral hall temperature.
Why it matters on shift
Rear-door coils support higher-density air-cooled servers, or capture the 20 to 30% air-cooled residual heat of direct-to-chip liquid racks, without modifying internal server motherboards or overloading perimeter CRAHs.
Illustrative operational example
An illustrative 45 kW rack uses a passive rear-door coil supplied with 20°C water (safely above a 15°C hall dew point) to cool 40°C server exhaust back to 22°C before it enters the aisle.
Scope, code & safety boundary
Rear-door coils must always receive water above room dew point unless specifically designed with condensate drainage; swinging a heavy wet door also requires flexible hoses rated for repeated hinge cycles.
Related courses & interactive lab practice
High-density AI cooling & commissioning
Air, chilled-water & liquid cooling
Practice live readings and switching in "120 kW GPU Direct-to-Chip CDU & Strainer Lab" with no login required.