RackscaleData Center Institute
Search & browse all 146 entries

Rear-Door Heat Exchanger (RDHx)

#rear-door-heat-exchanger
Also called
  • RDHx
  • passive rear-door coil
  • active rear-door cooler

Plain-English definition

A hinged liquid-cooled finned coil mounted in place of a cabinet's standard rear mesh door so hot server exhaust air passes directly through chilled-water or TCS tubes and re-enters the room at near-neutral hall temperature.

Why it matters on shift

Rear-door coils support higher-density air-cooled servers, or capture the 20 to 30% air-cooled residual heat of direct-to-chip liquid racks, without modifying internal server motherboards or overloading perimeter CRAHs.

Illustrative operational example

An illustrative 45 kW rack uses a passive rear-door coil supplied with 20°C water (safely above a 15°C hall dew point) to cool 40°C server exhaust back to 22°C before it enters the aisle.

Scope, code & safety boundary

Rear-door coils must always receive water above room dew point unless specifically designed with condensate drainage; swinging a heavy wet door also requires flexible hoses rated for repeated hinge cycles.

Related courses & interactive lab practice

AdvancedRS-203~85 min open lessons
AI Density Lab

High-density AI cooling & commissioning

BeginnerRS-103~85 min open lessons
Thermal Reality

Air, chilled-water & liquid cooling

Free interactive simulator
Campus Shift · 6-Mission Browser Lab

Practice live readings and switching in "120 kW GPU Direct-to-Chip CDU & Strainer Lab" with no login required.

Primary standards & technical references

Practice with the equipment

Try this concept in a live scenario.

Walk through six free guided browser missions in Campus Shift, or study all nine self-paced courses from Beginner to Advanced at $399 self-paced tuition ($1,600 list, save $1,201).