Relative Humidity (RH)

#relative-humidity
Also called
  • RH
  • percent relative humidity
  • hall humidity

Plain-English definition

The percentage ratio of actual water-vapor partial pressure in air to the maximum saturation vapor pressure air could hold at that exact dry-bulb temperature. Because warm air can hold much more moisture, heating air across a server lowers its relative humidity even when absolute moisture stays constant.

Why it matters on shift

Excessively low humidity increases electrostatic-discharge precautions, while excessive relative humidity accelerates hygroscopic dust bridging and copper/silver corrosion on circuit boards, especially if corrosive gases are present.

Illustrative operational example

Air entering a server at an illustrative 20°C and 50% RH (9.3°C dew point) exits the server rear at 34°C with the exact same 9.3°C dew point, but its relative humidity drops to roughly 22%.

Scope, code & safety boundary

Current ASHRAE Chapter 20 Table 1 note (n) sets recommended upper RH conditionally: up to 70% RH only in verified low-corrosion (G1) environments, versus 50% RH where corrosion risk is higher or unverified, not a blanket 60% rule.

Related courses & interactive lab practice

BeginnerRS-103~85 min open lessons
Thermal Reality

Air, chilled-water & liquid cooling

BeginnerRS-101~86 min open lessons
The Critical Floor

Facility, rack & safety foundations

Free interactive simulator
Campus Shift · 6-Mission Browser Lab

Practice live readings and switching in "35 kW Hot/Cold Aisle Containment Lab" with no login required.

Primary standards & technical references

Practice with the equipment

Try this concept in a live scenario.

Walk through six free guided browser missions in Campus Shift, or study all nine self-paced courses from Beginner to Advanced at $399 self-paced tuition ($1,600 list, save $1,201).