Stratified Chilled-Water Thermal Storage Tank (TES Buffer)
Plain-English definition
An insulated vertical vessel connected to the chilled-water loop that separates dense cold supply water at the bottom from lighter warm return water at the top across a thin natural density boundary (thermocline), supplying continuous cooling while chillers restart after an electrical disturbance.
Why it matters on shift
Even when UPS batteries keep servers and pumps online through a blackout, mechanical chillers drop offline during generator transfer; thermal storage bridges those critical minutes so high-density halls do not overheat.
Illustrative operational example
On North Campus, an illustrative 50,000-gallon stratified tank with an 11.5°C lower supply zone provides roughly 8 minutes of chilled-water ride-through while standby generators synchronize and chillers re-stage.
Scope, code & safety boundary
Excessive charging or discharging velocity through damaged internal diffusers destroys stratification by mixing warm and cold layers, cutting usable ride-through time sharply.