Low Delta-T Syndrome (Collapsed Chilled-Water Split)
Plain-English definition
A degraded hydronic operating condition in which chilled water returns to the central plant much cooler than designed (shrinking the return-minus-supply temperature split), so pumps and chillers hit maximum volumetric flow capacity long before reaching their rated megawatt cooling capacity.
Why it matters on shift
Low Delta-T forces operators to start extra chillers and run circulation pumps near 100% speed during moderate loads, starving hydraulically remote halls of differential pressure and inflating campus PUE.
Illustrative operational example
Suppose an illustrative plant designed for a 12°C split (12°C supply / 24°C return) degrades to a 6°C split (12°C / 18°C) from leaking bypass valves and fouled coils: moving the same heat now demands double the water flow.
Scope, code & safety boundary
Common root causes include fouled heat-exchanger surfaces, oversized or leaking control valves, air-side bypass, and supply-air setpoints pushed colder than coil design capability.