Actuator Saturation (100% Output) and Control Loop Hunting
Plain-English definition
Control-loop pathologies in which a valve, damper, or fan command either pegs at 100% full output without achieving setpoint (actuator saturation) or swings back and forth continuously around setpoint (hunting) due to aggressive PID gains, oversized valves, or sensor lag.
Why it matters on shift
When a CRAH chilled-water valve is already saturated at 100% open, lowering the air temperature setpoint accomplishes nothing; operators must look upstream at loop ΔP, supply water temperature, or containment bypass.
Illustrative operational example
If an illustrative Hall A CRAH shows 100% chilled-water valve command while discharge air drifts up to 24°C, the coil is starved of water flow or cold primary CHW rather than mis-set on air temperature.
Scope, code & safety boundary
Continuous valve or fan hunting wears out mechanical linkages and destabilizes header pressure across neighboring pods; place oscillating loops under tuned deadbands per site controls engineering.