Two-Way and Three-Way Modulating Hydronic Control Valve
Plain-English definition
Motorized proportional valves positioned from 0 to 100% by BMS controllers to regulate liquid flow through cooling coils and heat exchangers: two-way valves throttle flow directly for variable-speed pumping, while three-way valves divert or mix flow across economizer bypass paths.
Why it matters on shift
Properly sized two-way valves let variable-speed pumps slow down at part load, while integrated three-way bypass valves isolate outdoor economizer coils instantly whenever ambient air exceeds return water temperature.
Illustrative operational example
In the illustrative Central Plant lab at 36.0°C outdoor dry-bulb, the integrated 3-way WSE valve bypasses the dry coil completely so hot ambient air cannot heat 24.0°C return water, then opens once Stage 1 wetting lowers the coil floor to 20.4°C.
Scope, code & safety boundary
Verify spring-return or supercapacitor fail-safe valve positions (fail-open vs fail-last) for critical cooling coils so a lost control transformer does not shut chilled water off to live racks.