Carbon Usage Effectiveness (CUE, ISO/IEC 30134-8) and Energy Reuse Factor (ERF, ISO/IEC 30134-6)
Plain-English definition
Companion ISO/IEC 30134 metrics extending PUE and WUE: Carbon Usage Effectiveness (ISO/IEC 30134-8, kg CO2e divided by IT kWh) tracks operational carbon intensity per unit of compute energy, while Energy Reuse Factor (ISO/IEC 30134-6) measures exported waste heat reused outside the data center boundary.
Why it matters on shift
Warm 40°C to 50°C return water from liquid-cooled AI racks makes district-heating export practical (improving ERF without changing PUE itself), while hourly grid carbon intensity explains why two identical-PUE halls have very different CUE footprints.
Illustrative operational example
In an illustrative Nordic liquid-cooled facility consuming 20,000 MWh total (16,500 MWh IT) and exporting 5,000 MWh of warm FWS heat to a municipal district loop, PUE stays 1.21 while ERF reaches 5,000 ÷ 20,000 = 0.25.
Scope, code & safety boundary
Per ISO/IEC 30134-6, ERF ranges from 0 to 1.0 rather than subtracting exported heat inside PUE. Keep PUE, WUE, CUE, and ERF distinct rather than inventing proprietary subtracted PUE numbers.