Facility Water System (FWS)

#facility-water-system
Also called
  • FWS
  • primary building water loop
  • ASHRAE W-class facility water

Plain-English definition

In ASHRAE and Open Compute liquid-cooling architecture, the building-side piping circuit that delivers cooling water from central chillers, cooling towers, or dry coolers up to the primary side of a Coolant Distribution Unit (CDU), remaining hydraulically isolated from IT racks.

Why it matters on shift

Separating the large-volume Facility Water System from the clean rack loop protects microscopic cold-plate channels from building-pipe scale and bounds maximum fluid volume inside the white space.

Illustrative operational example

ASHRAE defines facility-water supply classes such as W17, W27, W32, and W40; an illustrative W27 loop supplies up to 27°C building water to CDUs so dry or adiabatic coolers can run compressor-free most of the year.

Scope, code & safety boundary

Never cross-connect Facility Water System piping directly into server cold-plate manifolds unless the system is explicitly engineered as a single-loop filtered architecture approved by the IT OEM.

Explanatory diagram · CDU skid, duplex strainers & rack quick-disconnectsFacility Water System (FWS) vs Technology Cooling System (TCS)
Three-zone liquid cooling schematic showing 12.0 degrees Celsius Facility Water System plant piping on the left, a CDU stainless plate heat exchanger with 25 micron strainer and dew-point guard in the center, and a 24.0 degrees Celsius Technology Cooling System rack manifold loop on the right.

A Coolant Distribution Unit (CDU) transfers heat across a stainless plate heat exchanger while keeping building chilled water physically separate from the filtered, chemistry-controlled coolant inside server cold plates.

Read plain-text walkthrough of this diagram

Zone 1 shows the building Facility Water System supplying 12.0 degrees Celsius chilled water and returning 19.0 degrees Celsius water via a modulating two-way valve without entering white-space racks. Zone 2 shows the CDU 316L stainless brazed-plate heat exchanger, N+1 variable-speed pumps, 25 micron strainer, and dew-point guard holding supply at least 3.0 degrees Celsius above the 13.8 degrees Celsius hall dew point. Zone 3 shows the Technology Cooling System delivering 24.0 degrees Celsius clean inhibited coolant across quick-disconnect valves to GPU and CPU cold plates (78% heat) while air cooling removes the remaining 22% rack heat.

Related courses & interactive lab practice

AdvancedRS-203~85 min open lessons
AI Density Lab

High-density AI cooling & commissioning

BeginnerRS-103~85 min open lessons
Thermal Reality

Air, chilled-water & liquid cooling

Free interactive simulator
Campus Shift · 6-Mission Browser Lab

Practice live readings and switching in "120 kW GPU Direct-to-Chip CDU & Strainer Lab" with no login required.

Primary standards & technical references

Practice with the equipment

Try this concept in a live scenario.

Walk through six free guided browser missions in Campus Shift, or study all nine self-paced courses from Beginner to Advanced at $399 self-paced tuition ($1,600 list, save $1,201).