Technology Cooling System (TCS)

#technology-cooling-system
Also called
  • TCS
  • secondary IT coolant loop
  • rack liquid loop

Plain-English definition

The closed, tightly filtered secondary liquid circuit that circulates high-purity treated water or an inhibited water-glycol mixture between the secondary side of a Coolant Distribution Unit, row/rack manifolds, and the cold plates inside IT servers.

Why it matters on shift

Because cold-plate microchannels can measure fractions of a millimeter across, TCS fluid cleanliness, pH, inhibitor chemistry, and dew-point temperature control directly govern accelerator reliability and hardware warranties.

Illustrative operational example

In the illustrative Hall D Row 8 pod, the TCS circulates 25 µm-filtered inhibited PG25 coolant at 23.0°C and 25.3 psi manifold differential pressure across eight 120 kW GPU racks.

Scope, code & safety boundary

Every wetted metal and elastomer in the TCS loop (wetted stainless steel, copper cold plates, EPDM hoses, and brazed joints) must match the approved wetted-materials compatibility list to prevent galvanic corrosion.

Explanatory diagram · CDU skid, duplex strainers & rack quick-disconnectsFacility Water System (FWS) vs Technology Cooling System (TCS)
Three-zone liquid cooling schematic showing 12.0 degrees Celsius Facility Water System plant piping on the left, a CDU stainless plate heat exchanger with 25 micron strainer and dew-point guard in the center, and a 24.0 degrees Celsius Technology Cooling System rack manifold loop on the right.

A Coolant Distribution Unit (CDU) transfers heat across a stainless plate heat exchanger while keeping building chilled water physically separate from the filtered, chemistry-controlled coolant inside server cold plates.

Read plain-text walkthrough of this diagram

Zone 1 shows the building Facility Water System supplying 12.0 degrees Celsius chilled water and returning 19.0 degrees Celsius water via a modulating two-way valve without entering white-space racks. Zone 2 shows the CDU 316L stainless brazed-plate heat exchanger, N+1 variable-speed pumps, 25 micron strainer, and dew-point guard holding supply at least 3.0 degrees Celsius above the 13.8 degrees Celsius hall dew point. Zone 3 shows the Technology Cooling System delivering 24.0 degrees Celsius clean inhibited coolant across quick-disconnect valves to GPU and CPU cold plates (78% heat) while air cooling removes the remaining 22% rack heat.

Related courses & interactive lab practice

AdvancedRS-203~85 min open lessons
AI Density Lab

High-density AI cooling & commissioning

Free interactive simulator
Campus Shift · 6-Mission Browser Lab

Practice live readings and switching in "120 kW GPU Direct-to-Chip CDU & Strainer Lab" with no login required.

Primary standards & technical references

Practice with the equipment

Try this concept in a live scenario.

Walk through six free guided browser missions in Campus Shift, or study all nine self-paced courses from Beginner to Advanced at $399 self-paced tuition ($1,600 list, save $1,201).