Waterside Economizer (WSE)
Plain-English definition
A heat-rejection coil or plate-and-frame heat exchanger arrangement that uses cool outdoor ambient conditions, via a cooling tower, dry cooler, or adiabatic fluid cooler, to pre-cool or fully cool return chilled water before or instead of running mechanical chiller compressors.
Why it matters on shift
In series pre-cooling plants, every degree removed by the economizer reduces mechanical lift on downstream chillers, allowing compressors to unload or stage off for substantial PUE savings.
Illustrative operational example
In our illustrative 8 MW heatwave scenario (24.0°C return CHW, 36.0°C DB / 18.5°C WB), dry WSE mode locks out in bypass, whereas Stage 1 adiabatic wetting pre-cools return water to 20.6°C so two chillers hold 12.1°C CHW at PUE 1.16.
Scope, code & safety boundary
Whenever outdoor heat-sink temperature plus approach exceeds return chilled-water temperature, a 3-way bypass valve must lock out the economizer coil so ambient air does not add heat to the return loop.
Passive heat-rejection equipment always leaves warmer than its outdoor sink floor by a positive approach temperature: dry coolers approach outdoor dry-bulb, while evaporative towers and adiabatic coolers approach outdoor wet-bulb.
Read plain-text walkthrough of this diagram
Two-column comparison at an illustrative outdoor condition of 32.0 degrees C dry-bulb and 20.0 degrees C wet-bulb (roughly 32% relative humidity at sea level). Column 1 (Dry Fluid Cooler) uses zero air-side evaporation water and is bounded by the 32.0 degrees C dry-bulb floor, leaving at an illustrative 37.0 degrees C (+5.0 degrees C approach). Column 2 (Cooling Tower / Adiabatic Evaporative) evaporates water to lower the air-side sink to the 20.0 degrees C wet-bulb floor, leaving at an illustrative 24.5 degrees C (+4.5 degrees C approach). Neither passive system can cool fluid below its respective sink floor without mechanical chiller compressor work.
Related courses & interactive lab practice
Energy, water & capacity accounting
Air, chilled-water & liquid cooling
Practice live readings and switching in "35 kW Hot/Cold Aisle Containment Lab" with no login required.
Primary standards & technical references