Wet-Bulb Temperature (WB)

#wet-bulb-temperature
Also called
  • WB
  • ambient wet-bulb
  • adiabatic saturation temperature

Plain-English definition

The lowest temperature air can reach at constant pressure through water evaporation into a moving airstream, classically measured with a water-wetted wick thermometer. In dry climates, wet-bulb sits far below dry-bulb; at 100% relative humidity, wet-bulb and dry-bulb are equal.

Why it matters on shift

Outdoor wet-bulb temperature establishes the thermodynamic floor for open cooling towers and wetted adiabatic fluid coolers: evaporation chills water well beneath hot outdoor dry-bulb while leaving water strictly warmer than ambient wet-bulb.

Illustrative operational example

In the illustrative 36.0°C dry-bulb / 18.5°C wet-bulb heatwave lab, wetting Stage 1 adiabatic pads lets the waterside economizer pre-cool 24.0°C return water down toward a 20.4°C approach floor, strictly above 18.5°C wet-bulb.

Scope, code & safety boundary

Designers size evaporative heat-rejection plants around extreme coincidence wet-bulb weather data, not annual averages, because high wet-bulb hours coincide with peak chiller condensing pressures.

Explanatory diagram · Outdoor economizer coils, cooling towers & chiller yardDry-bulb ceiling vs wet-bulb evaporative floor (PUE and WUE)
Psychrometric comparison chart showing 34.0 degrees Celsius outdoor dry-bulb above 28.0 degrees Celsius plant return water while wet-bulb sits at 21.0 degrees Celsius, paired with cool-dry, hot-arid, and hot-humid PUE and WUE operating regimes.

Dry coolers reject heat only down toward outdoor dry-bulb air temperature. Evaporative towers and adiabatic pads can cool water closer to wet-bulb temperature on hot dry days, trading water consumption (WUE) for lower chiller power (PUE).

Read plain-text walkthrough of this diagram

Left chart compares 34.0 degrees Celsius dry-bulb air, 28.0 degrees Celsius plant return water, and 21.0 degrees Celsius wet-bulb temperature at 30% relative humidity (13.0 degrees Celsius wet-bulb spread). Because 28.0 degrees Celsius water is cooler than 34.0 degrees Celsius dry air, dry free cooling locks out, whereas evaporative cooling approaches wet-bulb plus 3.5 degrees Celsius approach (~24.5 degrees Celsius water). Right panel compares Cool Dry weather (12.0 degrees Celsius DB, dry economizer, near-zero water), Hot Arid weather (34.0 degrees Celsius DB / 21.0 degrees Celsius WB, PUE improves from 1.29 to 1.21 while WUE rises from 0.08 to 0.94 L/kWh), and Hot Humid weather (31.0 degrees Celsius DB / 28.5 degrees Celsius WB, evaporation stalls and chillers carry full mechanical lift).

Related courses & interactive lab practice

IntermediateRS-302~75 min open lessons
Resource Ledger

Energy, water & capacity accounting

BeginnerRS-103~85 min open lessons
Thermal Reality

Air, chilled-water & liquid cooling

Free interactive simulator
Campus Shift · 6-Mission Browser Lab

Practice live readings and switching in "35 kW Hot/Cold Aisle Containment Lab" with no login required.

Primary standards & technical references

Practice with the equipment

Try this concept in a live scenario.

Walk through six free guided browser missions in Campus Shift, or study all nine self-paced courses from Beginner to Advanced at $399 self-paced tuition ($1,600 list, save $1,201).