Wet-Bulb Temperature (WB)
Plain-English definition
The lowest temperature air can reach at constant pressure through water evaporation into a moving airstream, classically measured with a water-wetted wick thermometer. In dry climates, wet-bulb sits far below dry-bulb; at 100% relative humidity, wet-bulb and dry-bulb are equal.
Why it matters on shift
Outdoor wet-bulb temperature establishes the thermodynamic floor for open cooling towers and wetted adiabatic fluid coolers: evaporation chills water well beneath hot outdoor dry-bulb while leaving water strictly warmer than ambient wet-bulb.
Illustrative operational example
In the illustrative 36.0°C dry-bulb / 18.5°C wet-bulb heatwave lab, wetting Stage 1 adiabatic pads lets the waterside economizer pre-cool 24.0°C return water down toward a 20.4°C approach floor, strictly above 18.5°C wet-bulb.
Scope, code & safety boundary
Designers size evaporative heat-rejection plants around extreme coincidence wet-bulb weather data, not annual averages, because high wet-bulb hours coincide with peak chiller condensing pressures.
Dry coolers reject heat only down toward outdoor dry-bulb air temperature. Evaporative towers and adiabatic pads can cool water closer to wet-bulb temperature on hot dry days, trading water consumption (WUE) for lower chiller power (PUE).
Read plain-text walkthrough of this diagram
Left chart compares 34.0 degrees Celsius dry-bulb air, 28.0 degrees Celsius plant return water, and 21.0 degrees Celsius wet-bulb temperature at 30% relative humidity (13.0 degrees Celsius wet-bulb spread). Because 28.0 degrees Celsius water is cooler than 34.0 degrees Celsius dry air, dry free cooling locks out, whereas evaporative cooling approaches wet-bulb plus 3.5 degrees Celsius approach (~24.5 degrees Celsius water). Right panel compares Cool Dry weather (12.0 degrees Celsius DB, dry economizer, near-zero water), Hot Arid weather (34.0 degrees Celsius DB / 21.0 degrees Celsius WB, PUE improves from 1.29 to 1.21 while WUE rises from 0.08 to 0.94 L/kWh), and Hot Humid weather (31.0 degrees Celsius DB / 28.5 degrees Celsius WB, evaporation stalls and chillers carry full mechanical lift).
Related courses & interactive lab practice
Energy, water & capacity accounting
Air, chilled-water & liquid cooling
Practice live readings and switching in "35 kW Hot/Cold Aisle Containment Lab" with no login required.
Primary standards & technical references